Extremely
Low Power Consumption
The power consumption of the 505U is very small as it conserves power
by reverting to ”sleep” mode between transmissions. The 505U can
be powered from an external 12 VDC supply, or it may be optionally fitted
with internal AA batteries which will power the unit for more than four
years. The 505U unit provides an internal alarm on low battery voltage
- this alarm may be transmitted by radio.
Weatherproof IP65 Enclosure
The 505U is enclosed in a heavy duty painted aluminium enclosure, weather-proofed
to IP65. Signal and power connections to the unit are made via
a weatherproof connector.
Compatible with 105U
The 505U is compatible with the 105U range of radio telemetry units*;
105U units may be used to output the process signals, or act as a network
master unit to connect to an intelligent host such as a PC or PLC. 105U
units may also be used as repeaters to extend radio range - up to five
intermediate 105U modules may be used as repeaters in any radio path.
More than 10 000 505U units may operate together in a single system.
(*Refer to 105U product literature)
Inputs
The 505U unit will accept digital, pulse and analogue input signals,
and will transmit the value of an input when the value changes. The
input value is also transmitted if the signal has not changed within
a pre-configured update time (configurable 1 minute to 5 days). Pulse
signals use the same input connection as digital inputs.
Alarm and Status Signals
The 505U will connect to digital inputs such as alarm or status signals
which are voltage free contacts or 0-5 VDC signals. Whenever the digital
signal changes (off to on, or on to off) the 505U will interrupt its
sleep mode and immediately transmit the signal value. For digital inputs,
there is a separate update time when the digital signal is active (on).
For example, an alarm input may update only every day when it is inactive,
but update every minute when it is active. This feature allows a large
number of 505U units to share the same radio channel. As well
as the external digital inputs, there are two internal digital “inputs”
- low battery voltage and analogue setpoint status.
Pulse Signals
The 505U will accept pulse signals up to 100 Hz, suitable for metering
applications. Whenever a pulse input is detected, the 505U will interrupt
its sleep mode and increase its internal pulse counter. The totalised
pulse count is transmitted whenever the count has changed by a pre-configured
amount. Transmissions will also occur after the update time. By
transmitting the totalised pulse count, the 505U ensures that individual
pulses are not lost, Should a radio transmission not be successful,
the pulse count is still held in the 505U, and the totalised value will
be updated on the next transmission. Change transmissions may be disabled
if the pulse rate exceeds a pre-configured amount, to prevent the radio
channel becoming congested during peak periods.
Analogue Signals
The 505U-2 model has one 0-20 mA (0-10 / 4-20 / 0-20 mA) analogue input.
The analogue signal may be externally or loop powered - the 505U generates
a 12VDC loop supply. During sleep mode, the loop supply is switched
off. After a pre-configured sleep period, the analogue loop supply is
activated, and the analogue measurement is taken. A warm-up time may
be configured to allow the analogue loop to stabilise before the measurement
is taken. If the sleep period is set to zero, then the 505U does not
revert to sleep mode, and it will continually measure the analogue signal
- note that this is only suitable where the 505U is powered from an
external supply. Once the analogue measurement is taken, the 505U will
transmit its value if it has changed since the last measurement. A sensitivity
value is configured (0.8 - 50%) to determine the minimum change to cause
a transmission. In addition, the analogue value will be transmitted
if the update time has been exceeded. Configurable setpoint values
may be used to generate an internal alarm status which may also be transmitted.
Configuration and Diagnostics
Configuration is easily performed by connecting a PC to an RS232 port
on the 505U module. The configuration software which is provided
with the unit, also includes dianostic functions.
Specifications
General
- Environmental -20 to
60degC 0 - 99% RH
- EMC compliant 89/336
EEC, AS3548
- Housing - IP65 painted
aluminium enclosure 160 x 64 x 36 mm
- Weatherproof connector
for external connections.
- BNC connector for aerial
or coaxial cable connection.
- LED indicators - Radio
TX, Operation OK
Power Supply
- External supply 11.5-15.0
VDC overvoltage/reverse power protected.
- Power consumption (12VDC)
-
quiescent (sleep mode) 120µA
operating mode 10mA + analogue loop
during radio transmission (100 msec)
170mA @ 250mW
100mA @ 100mW
50mA @ 10mW
- Internal battery supply
(505U-x-B only)
3 x AA lithium 3.5V 6 amphour nominal 4.1 year service life
2 x AA lithium 3.5V 4 amphour nominal 2.7 year service life
3 x AA alkaline 1.5V 2 amphour nominal 1.4 year service life
- Power consumption (internal
battery supply)
quiescent (sleep mode) 2.9mA-hour per day
analogue sample (5 sec warmup, 20mA) 120µA-hour during radio transmission
22µA-hour @ 250mW
15µA-hour @ 100mW
10µA-hour @ 10mW
- Analogue loop supply
internally generated 10-12VDC, 50mA
- Internal monitoring of
battery low voltage status - may be transmitted to remote modules
as an “input”.
- Power consumption increases
for pulse inputs > 1Hz.
Input Types
|
I/O
|
Power
Supply
|
Value
|
|
Digital
|
External
|
Status
|
|
Pulse
|
External
|
Count
|
|
Analogue
|
External
|
Analogue
|
|
Setpoint
|
Internal
|
Status
|
|
Battery low Volts
|
Internal
|
Status
|
Digital/Pulse Input
- 505U-1 one input
- 505U-2 two inputs
- suitable for voltage
free contacts / NPN
Digital Inputs
- transmitted as digital
status, debounce time 0.5 secs.
- status transmission on
change of input signal and on time elapsed since last transmission
- update time period 1 min - 5.3 days, a separate update time may
be configured for faster updates when the digital input is “on”
Pulse Input
- max rate 100 Hz (5 msec
on time), transmitted as pulse count transmissions occur when count
change exceeds configured amount, or on time elapsed since last transmission
- update time 1 min - 5 days - change transmissions may be suspended
if pulse rate exceeds a configured value to reduce radio traffic.
- Up/Down Pulse Input (505U-2
only) - The two pulse inputs may be configured to a single count,
to suit quadrature or incremental shaft encoder transducers.
Analogue Input (505U-2 only)
- 0 to 20 mA (4 - 20mA,
0 - 10mA) “floating” differential input
- common mode voltage 15V
- resolution 12 bit
- accuracy < 0.1%
- analogue measurement
continuous or sampled - sample time configurable 1 min - 5 days
- transducer warm-up time
configurable 1 - 59 sec
- analogue value transmitted
on change of input signal or time elapsed since last transmission
- change sensitivity configurable from 0.8 to 50%, update time configurable
from 1 min - 5 days
Setpoint Status
- high and low setpoints
generate internal digital status - setpoint status sets (on) when
analogue value < low setpoint and resets (off) when analogue value
> high setpoint status transmitted as per digital input
Serial Port
- RS232 DB9 female DCE,
used for configuration and diagnostics
Radio Transmitter
- Synthesised transmitter
- Frequency range 405 -
490 MHz.
- Channel spacing 12.5KHz
- Frequency configurable
range 10MHz
- Transmitter power (factory
set) -
500mW with 3dB aerial
100mW / 10mW 0dB aerial
- For 2 x AA battery supply,
max power is 100mW
- Conforms to EN 300 220,
MPT1329, AS4268.2, NZ RFS29
- Line of sight range -
10km (6 mls) @ 500mW
5km @ 100mW
2km @ 10mW
- Each transmission may
be configured to be sent 1 to 5 times.
Product Types
- External 12VDC supply
only -
505U-1-E (one digital/pulse input)
505U-2-E (two digital/pulse inputs plus one analogue input)
- Internal battery supply
only (batteries not included) -
505U-1-B (one digital/pulse input)
505U-2-B (two digital/pulse inputs plus one analogue input)
|