Wireless connectivity between different FieldBus protocols - Profibus, Ethernet, Modbus, DF1, DeviceNet, Modbus Plus.
Interface between Wireless I/O and DCS/PLC/HMI
The 105U-G Wireless gateway products provide a wireless interface between various data buses used in process and automation applications. The 105U-G includes an integral radio transceiver, and transfers transducer and control signals (I/O) using a highly secure and highly reliable radio protocol.
The 105U radio protocol is designed for very efficient radio usage, with configurable communications based on event reporting (I/O change), update times and/or poll response. Other features are:
- high security data encryption
- automatic acknowledgment and error-correction,
- peer to peer addressing, and
- mulitple path routing
|
|
Applications include:
- The 105U-G interfaces between 105U wireless I/O and various data buses. Connect wireless I/O to PLC's, DCS, SCADA or Internet.
- Wireless extension of factory automation buses such as Profibus and Ethernet.
- Wireless interconnectivity between different data buses - Ethernet to Profibus to Modbus to DF1.
The 105U-G modules also have eight on-board discrete I/O, individually configurable as input or output.
Network configuration is performed with easy-to-use free software. I/O links are configured between different modules in the network.
Ordering information:
105U-G-MD1 Modbus Master, Modbus Slave, DF1 interface
105U-G-PR1 Profibus DP Slave interface
105U-G-ET1 Ethernet IP / Modbus TCP / HTTP-FTP-Email
105U-G-DE1 DeviceNet Slave interface
105U-G-M+1 Modbus Plus Slave interface
Specifications
Power Supply
- 9 - 30VDC / 12 - 24VAC
- Battery charging circuit included for 12V back-up battery, max charge current regulated to 1A
- Normal current drain
- Modbus / DF1 version 12V 150mA; 24V 90mA
- Profibus / Ethernet 12V 270mA; 24V 170mA
- Add 5mA per active I/O
- Current drain during radio transmission - add to above
- 12V 350mA; 24V 200mA
General
- Modbus/DF1 version
-20 to 60 degC, 0 - 99 %RH
- Profibus / Ethernet / DeviceNet / Modbus Plus
0 to 60 degC, 0 - 95 %RH
- EMC Compliant EN55022, EN50082-1, FCC Part 15
- Housing - extruded aluminium case 130 x 185 x 60 mm, DIN rail mounting, removable terminal blocks for ease of module replacement, terminals suitable for 2.5sqmm wire
- LED indication for processor OK, radio TX and RX, serial TX and RX, active status.
I/O Capacity
- Modbus / DF1 4300 I/O points (analog plus discrete)
- Profibus 416 I/O bytes
up to 1952 discrete inputs / 1952 discrete outputs
or up to 122 analog in / 122 analog out
- Ethernet 2048 bytes input and 2048 bytes output
up to 4300 discrete I/O points
or up to 1024 analog in / 1024 analog out
- DeviceNet 512 bytes input and 512 bytes output
up to 4300 discrete I/O
or up to 256 analog in / 256 analog out
- Modbus Plus 2048 bytes input and 2048 bytes output
up to 4300 discrete I/O
or up to 1024 analog in / 1024 analog out
- Register size 16 bit
- Number of remote 105U addresses 500
Radio Transceiver
- Single channel, synthesised, direct frequency modulation.
- Frequency 405-490 MHz, 12.5KHz channels, 10-500mW, 5W
220-230 MHz, 25KHz channels, 5W
869.525 MHz, 250KHz channel, 500mW
- Approved to EN 300 220, AS4268.2, RFS29
- Expected line-of-sight range, with unity gain antennas
10mW - 2km; 500mW - 5km(869Mz) / 10km (400MHz);
- 5W - 40km (220MHz) / 30km (400MHz)
- Range may be extended by up to four intermediate repeaters.
Radio Transmission
- Radio communications can be configured for combination of event reporting (change-of-value), update time, read/write blocks and poll response.
- Radio message includes system addressing, unit addressing, error-checking and configurable security encryption.
- Communication control includes message acknowledgments and up to four re-transmissions.
- Peer to peer addressing. Messages may be routed thru four intermediate repeater addresses.
- Fail-to-transmit and fail-to-receive alarms configurable
Modbus Specification
- Modbus RTU (binary), master / slave configurable.
- RS232 or RS485, 300 - 19200 bits/sec.
DF1 Specification
- Allen-Bradley DF1 full-duplex.
- RS232 only, 300 - 19200 bits/sec.
Profibus
- Profibus-DP Slave functionality according to EN 50170.
- RS-485 optically isolated with on-board DC/DC converter, automatic baudrate detection (9600 bit/s - 12 Mbit/s)
Ethernet
- 10/100 Mbit/s, RJ45 transformer isolated interface
- Modbus/TCP class 0, class 1 and partially class 2 slave
- EtherNet/IP level 2 I/O Server
- Embedded Web system (Dynamic HTTP), on-board file system (1.4MB flash disc), user downloadable web pages through FTP server, Email functionality (SMTP)
DeviceNet
- DeviceNet 2.0 Slave, optically isolated RS422 with selectable baudrate 125, 250 and 500 Kbit/sec.
Modbus Plus
- Modbus Plus Slave, optically isolated RS485 with standard baudrate of 1 Mbit/sec, global data base transactions with routing for up to six networks.
On-board I/O
- Eight discrete I/O, individually configurable as input or output. Inputs suitable for voltage free contacts.
- Outputs are FET, 30VDC 500mA.
Configuration & Diagnostics
- Configuration via free Windows software
- Diagnostics include on-line read/write of I/O registers, radio signal strength values from remote units, and off-line testing of data bus protocol.
|